Hangzhou Fuda Dehumidification Equipment Co., Ltd
|
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Heavy Duty Automatic 380V Industrial Dehumidifier with 8000m³/h Air Flow
Quick Detail:
Style: Refrigeration combined with Wheel adsorption
Desiccant Rotor: Sweden Proflute
Desiccant Rotor Material: Silica Gel Wheel
Rated Air Flow: 8000m³ /h
Supply Air Parameters: T=20 RH=30%
Dehumidifier Quality: High
Installed Power: 40.7kw
Voltage: 380V, 3 phase, 50Hz or as customer required
Certification: ISO9001:2008
Features: Economical, energy-saving
Usage: Air temperature and humidity control
General Description:
ZCB Series Fully Automatic Industrial Dehumidifier Customized removes humidity using both refrigeration and a desiccant rotor, so it can both control the humidity and temperature of the air independently in one packaged unit.
Operating Principles:
Supply Air Stream
Outside air is drawn into the unit using the supply fan. The warm, moist outside air first passes through filters and then the cooling coil where it is cooled. The air then goes through the desiccant wheel where the air is dehumidified and the temperature is raised. At last the air is delivered directly to the space or into an existing air handler.
Exhaust Air Stream
Exhaust air is used to provide energy recovery for the desiccant wheel and is drawn into the unit using the exhaust fan. The air filtered and then heated and humidified during the energy recovery process. The air is then heated while passing through the regeneration coil. The heated air removes the moisture that the desiccant wheel adsorbs from the process air stream.
Applications:
Specifications:
Main Parameters |
|
Model |
ZCB—8000 |
Total Process Airflow |
8000m3/h |
Fresh Airflow |
800 m3/h |
First Recirculated Airflow |
3200 m3/h |
Second Recirculated Airflow |
4000 h |
Rotor Regeneration Airflow |
1330m3/h |
Parameters of Output Air |
T≤23 RH≤30%-40% |
Regeneration Heating Power |
32kw |
The Power of Regeneration Fan |
1.1kw |
The Power of Blower |
7.5kw |
The Power of Driving Motor |
0.1kw |
Installed Power |
40.7kw |
Cooling Load |
42.9kw |